Testing Of Feeder Protection Relay (50/51, 50N/51N)
Feeder Protection Relay is tested with secondary injection set with
electronic meter.
. Ensure that the CT incoming on the Test Plug MMB01 is shorted before
inserting.
. Isolate the Relay Current Measuring Elements & Trip/.Alarm contacts by
inserting the Test Block MMB01.
. Connect correct polarity/rating of DC Voltage through Test Plug MMB01
to Relay. Ready “LED indicator” Should be illuminated.
. Connect the Relay to computer through Front RS232 Port or use the MM1
(Man Machine interface).
. Ensure Curve selection as required.
. Disable the instantaneous element and enable the time delayed element of
the Relay.
. Set the value and check start value for O/C protection.
. Inject single phase current into a convenient phase circuit and slowly
increase the current until the Pick-up LED lights.
. Connect the Relay time delayed output contacts to both trip the test set and
stop a timer.
. Set appropriate time setting.
. Inject single phase current into pole under test at a current level of “n” x
rated current (where “n” being the multiple of current setting of the Relay.
. Check operating time for the Relay.
. Inject single phase current into the pole under test at different current
levels.
. For instantaneous element operation, enable the instantaneous element of
the Relay.
. Adjust current setting for instantaneous element and connect instantaneous
trip output contact to trip the test set.
. Time delay element is set to operate in 4 s. The current level should be set,
and then suddenly applied. Test is done for each pole of Relay.
All readings are to be recorded on the test form.