ACH550 BASIC START UP GUIDELINE

ABB ACH 550 
If you want to program the ABB ACH 550 drive and you have the basic knowledge you can simply start with following basic settings. When using the default Macros such as HVAC Default or E-Bypass the External. Reference will be preset and should not need to be changed provided a voltage of 0-10 VDC or 4-20mA is to be used and is connected to AI1.
ABB ACH550 Basic Settings
Sr#
Group
Parameter
Description
Value
1
99
1
Language
English
2
99
2
Appl Macro
Hvac Default
3
99
5
Motor Nom Voltage
As required
4
99
6
Motor Nom Current
As required
5
99
7
Motor Nom Freq
As required
6
99
8
Motor Nom Speed
As required
7
99
9
Motor Nom Power
As required
8
13
1
Minimum AI1
20% for (4 to 20 mA)
0% for ( 0 to 10V)
9
16
1
Run Enable
As per drawing 
10
16
8
Start Enable
As per Drawing

11
20
3
Maximum Current
As required
12
20
7
Minimum Frequency
15 Hz (To be used for fans)                                                                                                                                                                                                                20 Hz (To be used for pumps and cooling towers using gearbox design fan)
13
20
6
Undervolatge
Enable
14
21
1
Start Function
Ramp to start
15
21
2
Stop Function
Ramp to stop
16
22
2
Acceleration time
30s
17
22
3
Deceleration Time
30s
18
22
4
Ramp Shape
Linear
19
26
5
U/F Ratio
Linear
20
30
2
Panel  Comm Err
Last Speed
21
30
5
Mot Thermal Port
Not Sel
22
30
17
Earth Fault
Enable
23
31
4
AR Overcurrent
Enable
24
31
5
AR Overvoltage
Enable
   This simplified start-up allows you to set the drive to run the process.