Following
point must be noted during physical checking before and after powering the
drive:
- The drive is securely mounted.
- Verify the physical and mechanical condition of VFD.
- Verify circuit breaker and contactor type, rating, and cabling
is correct.
- Verify the equipment data with drawing and
specification.
- Input power voltage matches drive rating..
- Input power connections are connected and are tight.
- All connection should be check according to approved
drawing.
- Motor and driven equipment are ready to start (i.e. No
mechanical obstructions)
- Proper grounding.
- Confirm all push buttons, indicating lights are
functioning properly.
- All auxiliary contacts and terminals are working
properly.
- All buttons are working on the LCD, tested for local
and auto control.
- Check analogue and digital signals inputs and output.
- Apply gradual frequency and check visually the speed of
motor.
- Control cables/ Wire insulation test @500 volt phase to
ground verified.
- Confirm parameters are programmed and ready.
- Input power branch circuit protection is in place (ie.
Fuses or circuit breaker)
- Motor connections are connected and are tight.
- Input power, motor and controls are each in separate
conduit runs (Recommended)
- Should know how with Ingress protection classes (IP
CLASS).