Saturday, July 16, 2016

Testing of TRIP CIRCUIT SUPERVISION RELAY (97)

Trip circuit supervision relay is tested with variable DC power supply, Variable Resistance, one Push button with set of NO + NC contacts and Electronic Timer. . Connect correct polarity/rating of DC Voltage to Relay (terminal # B9 & B10). Press the “Target Reset” button and check that all target LEDs lights up. . UNDER VOLTAGE TEST . Connect Variable DC power supply to Relay Breaker Voltage inputs: teminal B1 (+ve) & B2 (-ve). . Set the time to minimum in order to ease the test. . Short all the Relay Trip coil monitoring inputs. . Apply different Voltages and check that the undervoltage LED flashes pick –up) with voltage (see table below). The LED remains flashing, until the undervoltage condition disappears (drop out voltage). When the drop-out voltage is reached, and the set time elapses, the LED stop flashing and is lit permanently (fault memory function).


VOLTAGE  SETTING
PICK-UP VOLTAGE
(VOLTAGE FAILURE)
DROP-OUT VOLTAGE
(VOLTAGEOK)
50V
45V
55V
55V
50V
60V
60V
55V
65V
70V
65V
75V
90V
85V
95V
125V
118V
133V

.       TIME DELAY TEST
                .        Connect 125VDC  supply to Relay Breaker Voltage inputs: terminal B1                                        (+ve)  & B2 (-ve).
                .       Connect the Push button NC contacts to Relay Trip coil # 1 monitoring input
                                (terminal # B3) & Breaker Voltage input (terminal # B2).
                .       Connect the Breaker circuit OK “NO” output contacts to stop the timer.
                .       Set the Time Delay according to the table given below: and check that the                                     results in the table are complied with. Repeat the test using coil # 2 & 31/P’s.

TIME DELAY
SETTING
MINIMUM OPERATING TIME
MAXIMUM OPERATING TIME
DROP-OUT TIME
(OUTPUT RELAY)
200ms
200ms
240ms

400ms
400ms
440ms

600ms
600ms
640ms

1 s
1 s
1.04 s
100 – 150ms








                     